We hook a calibrated gauge to the little test valves on the device, close the shutoffs and see if each check holds. On an RP we also check the relief valve. The numbers go on the district's form.
Pricing
| Backflow size | Flat fee per backflow |
|---|---|
| Under 4" | $105 |
| 4" and larger | $175 |
Includes the test and filing with your water district. No hidden fees.
- Price$105 flat
- TimeUnder an hour
- SchedulingSame week
- FilingIncluded
Easiest way? Just call.
On every test
- Air inlet opens fully (PVB and SVB)
- Shutoff valves close tight
- Relief valve opens at the right point (RP)
- Each check valve holds pressure
- Test cocks and body show no leaks
The test gauge and why calibration matters
Every backflow test depends on a differential pressure gauge. It measures the small pressure differences across each check valve and, on an RP, the point where the relief valve opens. Those numbers decide whether your device passes.
A gauge that reads even slightly off can pass a bad device or fail a good one. That's why water districts require test gauges to be checked for accuracy on a regular schedule, and why our gauges are kept in calibration.
It's also why a test has to be done by a certified tester. Certification means the tester has been trained on the procedures and passed an exam on them. Your district won't accept a report without a certified tester's signature and the gauge details listed.
Step by step through an assembly test
The test starts with a quick look at the assembly: is it the right type, is anything cracked or leaking, are the test cocks in good shape. The tester flushes each test cock so grit doesn't skew the readings.
Then the downstream shutoff is closed and the gauge is connected. The tester checks the first check valve, then the second. On an RP the relief valve opening point is checked as well. Vacuum breakers get an air inlet test and a check valve test.
After the readings, the valves are reopened, the caps go back on and the tester looks for leaks. Most assemblies take between 20 and 45 minutes. Bigger devices or tight spots can add a little time.
The usual causes of a failed test
The most common reason a test fails is debris. Sand, rust flakes and bits of pipe sealant travel down the water main and get caught on a check valve seat, keeping it from closing all the way. A cleaning often fixes it.
Worn rubber is next. Check discs and o-rings harden and crack with age, heat and chlorine in the water. Rebuild kits replace those parts for a fraction of the cost of a new device.
Less often, a spring has weakened, a relief valve diaphragm has torn, or the body is cracked from freezing or impact. Springs and diaphragms are repairable. A cracked body usually means replacement. Whatever the cause, we show you the reading and explain it before any work starts.
What goes on the test report
Your water district judges compliance by the report, not the visit. The report shows the address, the device make, model, size and serial number, its location, and every reading taken.
It also carries the tester's certification and gauge details, plus the result: pass, fail, or pass after repair, with any replaced parts listed.
Districts don't all use the same form, and many have deadlines for submitting reports after a test. We take care of that part and send you a copy. Keep it somewhere easy to find, since escrow companies, landlords and city inspectors sometimes ask for it.
The parts the test depends on
An assembly has small valves called test cocks where the gauge connects, plus a shutoff valve on each end. If a test cock is clogged or a shutoff won't close fully, the test can't be done accurately.
We check these before starting. Clogged test cocks can often be cleared on the spot. A shutoff valve that won't seal may need repair before the device can be tested properly, and we'll explain it if that's the case.
Testing after repairs, moves and installs
Annual tests aren't the only ones. After any repair, the assembly must be retested. When a device is relocated or reinstalled, it's tested again. New devices get a startup test.
The procedure is the same each time, and each produces a report for the district. If we did the work, that follow-up test is part of the job.
If a reading is off
You see the readings and get a price for the fix before we do anything. See assembly repair.
Questions
How long does an assembly test take?
Most take 20 to 45 minutes per device, depending on size and access.
Can a device pass one year and fail the next?
Yes. Debris and wear build up over time, which is exactly why the test is yearly.
Is the gauge calibrated?
Yes. Districts require test gauges to be calibrated on a schedule, and ours are.
Will I see the readings?
Yes. They're on your copy of the report, and the tester can walk you through them on site.
Who gets the test results?
Your water district gets the report, and you get a copy too.
Do you need to shut my water off?
Only for a few minutes during the test. We'll let you know before we close the valves.
Why folks in Torrance call us
Backflow is what we do. Our testers are certified, our gauges are calibrated, and we send the report to your water district for you, every time.
No surprises on price: $105 for devices under 4 inches, $175 for 4 inches and up, and free quotes on everything else. We answer seven days a week, 6am to midnight, and emergencies around the clock.
Here's how a visit goes. We call or text when we're on the way, find the device, and get the test done. If it passes, that's it: we file the report and send you a copy. If it doesn't, we'll show you what's wrong, tell you the price and fix it if you want us to. Most folks around Torrance never need to be home for any of it.
Torrance and nearby
We do backflow assembly testing in Torrance, Redondo Beach, West Carson, Harbor Gateway, Lomita and Carson. We can usually come out this week.